SANS 10142 Testing Principles Series (6)
⚡ SANS 10142 Testing Principles Series
Test 6: Prospective Short-Circuit Current (PSC) — Proving the System Can Handle Fault Energy
Introduction
Up to now, we’ve confirmed:
- Test 1: Bonding is correct
- Test 2: Earth continuity is acceptable
- Test 3: Circuits are complete
- Test 4 & 5: Protection will operate under fault conditions
Now we move to a different but equally critical question:
👉 Can the system safely handle the fault current when it happens?
Because when a short circuit occurs…
👉 The current can rise to extremely high levels in milliseconds.
According to SANS 10142-1 (Clause 8.6 – Testing):
👉 The prospective short-circuit current (PSC) must be measured or determined to ensure that protective devices can safely interrupt the fault current.
🧠 1. Foundation (Understanding): What Are We Actually Testing?
⚡ What Is PSC?
PSC is the maximum current that can flow during a short circuit.
🔑 Types of Faults Considered
👉 Phase to Neutral (L–N)
👉 Phase to Phase (L–L) (where applicable)
🔍 What This Test Proves
👉 That the fault current will NOT exceed the breaking capacity of the protection device
⚠️ Why This Matters
If PSC is too high:
🚨 Breaker may fail to interrupt
🚨 Equipment damage occurs
🚨 Arc flash risk increases
🚨 Fire or explosion risk increases
🛠️ 2. Application (Doing): How Must the Test Be Done?
⚠️ IMPORTANT
👉 This test is conducted under live conditions
👉 Using a PSC / loop impedance tester
🔧 Measurement Method
PSC is typically determined by:
👉 Measuring loop impedance and calculating PSC
OR
👉 Using a tester that directly displays PSC
⚡ Typical Connection
For single-phase systems:
👉 Live → L
👉 Neutral → N
📊 Relationship Between PSC and Impedance
👉 PSC is inversely related to impedance:
- Low impedance → High fault current
- High impedance → Lower fault current
🎯 PASS REQUIREMENT
👉 Measured PSC must be:
🔥 LESS than the breaking capacity of the protective device
Example:
- Breaker rated at 6 kA
👉 PSC must be below 6 kA
⚡ 3. Mastery (Owning Responsibility): What Are the Limitations?
This is where professionals stand out.
🔍 The Professional Must Ask:
👉 What is the breaker breaking capacity?
👉 What is the supply strength?
👉 Is this near a transformer?
👉 Are there parallel supply paths?
👉 Has the installation been extended?
👉 Is the measured PSC the worst-case scenario?
⚠️ Critical Understanding
PSC is highest:
👉 Close to the transformer
👉 At the origin of the installation
And decreases further along the circuit.
⚠️ Common Mistakes
- Not measuring PSC at origin
- Ignoring breaker breaking capacity
- Confusing PSC with load current
- Assuming standard values
- Not considering supply variations
💡 Final Thought
Test 6 is about energy control.
Because during a fault:
👉 It’s not just about whether it trips…
👉 It’s about whether it survives the interruption.
At TDMI Training, we emphasise:
👉 Protection must not only operate
👉 It must withstand the fault safely
✅ The Standard
- Measure or calculate PSC
- Compare to breaker rating
- Verify equipment suitability
- Understand system conditions
👉 Because when a short circuit happens…
the system must contain it instantly.

Leave a comment